| On the Effect of Pressure Monitoring for Valve-induced Transient Flow in Water Transmission Lines |
|---|
|
학술지명 International Water Association
저자 최두용,김주환,배철호,김도환
발표일 2013-09-20
|
|
Pressure monitoring provides valuable insights for managing water supply systems bytracking time-dependent hydraulic transients. In this study, we report on two pressure-monitoringissues?sampling location and sampling interval?by analyzing a valve-induced transient event thatwas not recorded in the supervisory control and data acquisition (SCADA) system of a real watertransmission line in the south of Korea. Field measurement data show that the measured magnitude ofpressure is influenced by the sampling location, which depends on pipe connectivity and distance fromautomatic control valve, and by the sampling interval, which is sensitive to network size for wavepropagation. Based on the findings of the field experiments, a pressure-measurement method isproposed by employing numerical transient simulation and spectral analysis of pressure waves. |