| Optimization of a Raw Water Source Heat Pumpfor a Vertical Water Treatment Building |
|---|
|
학술지명 IJACR
저자 조용,윤린,오선희
발표일 2015-01-31
|
|
The optimum operation conditions of a raw water source heat pump for a vertical water treatmentbuilding were derived by changing operation parameters, such as temperature of thermal storagetank, temperature and inlet air °ow rate of the conditioned spaces, and circulating water °ow ratebetween thermal storage tank and air handling unit (AHU) through dynamic simulator of atransient system simulation program (TRNSYS). Minimum electric power consumption wasfound at temperature of thermal storage tank, which was ranged 18?23C for cooling season. Inheating season, temperature 40?45C brings the highest coe±cient of performance (COP) andtemperature range of 30?35C brings the lowest power consumption. When the temperature ofthe conditioned spaces was controlled between 27?28C for cooling season, and 18?20C forheating season the minimum electric power consumption was obtained. Inlet air °ow rate of1.1m3/h for the conditioned spaces shows the highest performance of the present system, ande??ects of circulating water °ow rate between thermal storage tank and AHU on minimum electricpower consumption of the system were negligible. |