Experimental study on leak-induced Vibration in Water Pipelines Using Fiber Bragg Grating Sensors 게시글의 제목, 학술지명, 저자, 발행일, 작성내용을 보여줌
Experimental study on leak-induced Vibration in Water Pipelines Using Fiber Bragg Grating Sensors
학술지명 Current Optics and Photonics 저자 김대길,박시웅,박형준,여찬일,배철호
발표일 2022-04-01

Leak detection is one of the most important challenges in condition monitoring of water pipelines.
Fiber Bragg grating (FBG) sensors offer an attractive technique to detect leak signals. In this paper, leak
measurements were conducted on a water distribution pilot plant with a length of 270 m and a diameter
of 100 mm. FBG sensors were installed on the pipeline surface and used to detect leak vibration signals.
The leak was demonstrated with 1-, 2-, 3-, and 4-mm diameter leak holes in four different pipe types.
The frequency response of leak signals was analyzed by fast Fourier transform analysis in real time.
In the experiment, the frequency range of leak signals was approximately 340?440 Hz. The frequency
shifts of leak signals according to the pipe type and the size of the leak hole were demonstrated at a
pressure of 1.8 bar and a flow rate of 25.51 m3/h. Results show that frequency shifts detected by FBG
sensors can be used to detect leaks in pipelines.